Thermocouple Module, 4 Channels
The Thermocouple Module monitors up to 4 channels of Type J, K, or T thermocouples. The temperature information is provided to the engine control system over SAE J1939 CAN bus. Temperature information can include exhaust temperature, winding temperature, and fluid temperature monitoring. All channels are fully isolated and measure temperatures at the same time. Temperature data is automatically sent over the CAN bus when power is applied. During set-up, the operator can configure the controller via the Axiomatic Electronic Assistant to suit a wide variety of applications. Integral diagnostics can flag open wire fault detection. CAN communications are via an isolated CAN interface with SAE J1939 protocol.
Our products are designed to be customized by our customers and can be thought of as product foundations. Find the foundational product(s) that you need in our catalog, add them to your quote cart, then explain your requirements for your project on the quote cart submission form. If you cannot find the foundational product, please tell us your requirements.
Technical Specifications
Thermocouple Module, 4 Channel, SAE J1939
Order Code
P/N: AXTC4
Input(s)
4 channels for thermocouple inputs (Type J, K, or T)
CAN Port(s)
1 SAE J1939 port
CAN Baud Rate
250 kbit/s
Operating Voltage
12V or 24Vdc nominal
Isolation
Full channel to channel isolation and isolation from CAN line, other inputs and power supply
Enclosure
High Temperature Nylon housing, TE Deutsch PCB Enclosure (EEC-325X4B)
4.62 x 5.24 x 1.43 inches
117.42 x 133.09 x 36.36 mm
Connection(s)
Deutsch DTM series 24 pin receptacle (DTM13-12PA-12PB-R008)
Protection Rating
IP67
Operating Temperature
-40 to 85 ºC
-40 to 185 ºF
Applications
Power Generator Sets
Accessories
PL-DTM06-12SA-12SB, Mating Plug KIT (DTM06-12SA, DTM06-12SB, 2 WM-12S, 24 Contacts, 18 Plugs)
AX070502, Axiomatic Electronic Assistant KIT (AX070501 USB-CAN Converter, 2 Cables, Installation Instructions)
AX070506K, Axiomatic Electronic Assistant KIT III (AX070506 USB-CAN Converter, 3 Cables, Installation Instructions)
Datasheet
User Manual
STEP File
Compliance
4 Inputs, 8 Proportional Outputs Valve Controller, CANopen®
20 Channel Thermocouple Scanner, Full Isolation, SAE J1939
4 Digital Inputs Modbus Router, Modbus TCP/IP, SAE J1939
4 Universal Signal Outputs CAN Controller, CANopen®, Compact
4 Universal Input CAN Controller, +5V/8V Reference with Feedback Signal, CANopen®
Wire Harness (DTP06-4S Mating Plug, 2m (6.5ft.) 12 AWG Unterminated Wires)
4 Inputs, 4 Outputs Isolated Controller, SAE J1939
2 RTD Inputs, 2 Outputs Intelligent Load Control Switch, CANopen®, Modbus RTU, Ethernet, Wi-Fi
12 Inputs, 12 Proportional & 2 Relay Outputs Controller, 2 SAE J1939, Ethernet